Gas Appliance OEM Settings Page

CHOOSE A DIFFERENT MANUFACTURER3


CHOOSE A DIFFERENT APPLIANCE

Burnham (U.S. Boiler) V903A (447 MBH)

Manufacturer:    Burnham (U.S. Boiler)
Appliance Series:    V
Appliance Model:    V903A
Burner Model:    301GAS
Difusser:    B
Air Tube:    14" B
OEM Air Tube #:    99597
Insertion Depth:    4 1/8
Input MBH:   447
Natural Gas Orifice:    31/64 (.484)
Propane Orifice:    25/64 (.391)
Air Setting:   30NG/35LP
Air Band:   4 slot
Head Bar:   -
Air Shutter:    Full
Manifold Pressure:    3.5NG/3.4LP
NOTES:    3 through 5 section boilers require 8" extended front plate P/N 6022909 and burner adapter plate P/N 602292311 (order from Burnham)