Gas Appliance OEM Settings Page
CHOOSE A DIFFERENT MANUFACTURER3CHOOSE A DIFFERENT APPLIANCE
Burnham (U.S. Boiler) V905A (808 MBH)
Manufacturer: | Burnham (U.S. Boiler) |
Appliance Series: | V |
Appliance Model: | V905A |
Burner Model: | 601GAS |
Difusser: | 11 |
Air Tube: | 14" B |
OEM Air Tube #: | 99597 |
Insertion Depth: | 4 1/8 |
Input MBH: | 808 |
Natural Gas Orifice: | 23/32 (.719) |
Propane Orifice: | 33/64 (.516) |
Air Setting: | 2 |
Air Band: | -- |
Head Bar: | - |
Air Shutter: | -- |
Manifold Pressure: | 3.5NG/3.6LP |
NOTES: | 3 through 5 section boilers require 8" extended front plate P/N 6022909 and burner adapter plate P/N 602292311 (order from Burnham) |