Gas Appliance OEM Settings Page

CHOOSE A DIFFERENT MANUFACTURER3


CHOOSE A DIFFERENT APPLIANCE

Burnham (U.S. Boiler) V907A (1198 MBH)

Manufacturer:   
Appliance Series:    V
Appliance Model:    V907A
Burner Model:    601GAS
Difusser:   
Air Tube:    14" D
OEM Air Tube #:    99600
Insertion Depth:    4 1/8
Input MBH:   1198
Natural Gas Orifice:    15/16 (.938)
Propane Orifice:   
Air Setting:   5
Air Band:   --
Head Bar:   -
Air Shutter:    --
Manifold Pressure:    3.6
NOTES:    3 through 5 section boilers require 8" extended front plate P/N 6022909 and burner adapter plate P/N 602292311 (order from Burnham)