Gas Appliance OEM Settings Page
CHOOSE A DIFFERENT MANUFACTURER3CHOOSE A DIFFERENT APPLIANCE
Burnham (U.S. Boiler) V907A (1198 MBH)
Manufacturer: | |
Appliance Series: | V |
Appliance Model: | V907A |
Burner Model: | 601GAS |
Difusser: | |
Air Tube: | 14" D |
OEM Air Tube #: | 99600 |
Insertion Depth: | 4 1/8 |
Input MBH: | 1198 |
Natural Gas Orifice: | 15/16 (.938) |
Propane Orifice: | |
Air Setting: | 5 |
Air Band: | -- |
Head Bar: | - |
Air Shutter: | -- |
Manifold Pressure: | 3.6 |