New Yorker Boiler Co. FR-122-W (150 MBH)

Manufacturer:    New Yorker Boiler
Appliance Series:    FR
Appliance Model:    FR-122-W
Burner Model:    EZGas Pro
Difusser:    9S
Air Tube:    10"
OEM Air Tube #:    Universal
Insertion Depth:    1 1/2
Input MBH:   150
Natural Gas Orifice:    I (.272)
Propane Orifice:    A (.234)
Air Setting:   50%
Air Band:   1 Slot
Head Bar:   -
Air Shutter:    blank
Manifold Pressure:    3.5
NOTES:   