Gas Appliance OEM Settings Page
CHOOSE A DIFFERENT MANUFACTURER3CHOOSE A DIFFERENT APPLIANCE
New Yorker Boiler Co. HGSI-DV (140 MBH)
Manufacturer: | New Yorker Boiler |
Appliance Series: | HGSI |
Appliance Model: | HGSI-DV |
Burner Model: | EZGas Pro |
Difusser: | 9S |
Air Tube: | 10" |
OEM Air Tube #: | Universal |
Insertion Depth: | 1 1/2 |
Input MBH: | 140 |
Natural Gas Orifice: | F (.257) |
Propane Orifice: | A (.234) |
Air Setting: | 45% |
Air Band: | 1 Slot |
Head Bar: | - |
Air Shutter: | -- |
Manifold Pressure: | 3.5NG/3.2LP |
NOTES: | NEED BURNER COVER FOR DIRECT VENT MODELS |