Gas Appliance OEM Settings Page
CHOOSE A DIFFERENT MANUFACTURER3CHOOSE A DIFFERENT APPLIANCE
Buderus G115-5-DV (140 MBH)
| Manufacturer: | Buderus Hydronic Systems |
| Appliance Series: | G115 |
| Appliance Model: | G115-5-DV |
| Burner Model: | EZGas Pro |
| Difusser: | B |
| Air Tube: | 12" |
| OEM Air Tube #: | 98896 |
| Insertion Depth: | 4 |
| Input MBH: | 140 |
| Natural Gas Orifice: | I (.272) |
| Propane Orifice: | #5 (.206) |
| Air Setting: | 50% |
| Air Band: | Air Boot |
| Head Bar: | - |
| Air Shutter: | -- |
| Manifold Pressure: | 3.5 |
| NOTES: | Must have gasket under ignitor and grommet in access cover: kit # GSKTKIT1 Only use welded flange burners with G115 boilers. G215 boilers not recommended. |