Gas Appliance OEM Settings Page
CHOOSE A DIFFERENT MANUFACTURER3CHOOSE A DIFFERENT APPLIANCE
Burnham (U.S. Boiler) V903A (447 MBH)
Manufacturer: | Burnham (U.S. Boiler) |
Appliance Series: | V |
Appliance Model: | V903A |
Burner Model: | 301GAS |
Difusser: | B |
Air Tube: | 14" B |
OEM Air Tube #: | 99597 |
Insertion Depth: | 4 1/8 |
Input MBH: | 447 |
Natural Gas Orifice: | 31/64 (.484) |
Propane Orifice: | 25/64 (.391) |
Air Setting: | 30NG/35LP |
Air Band: | 4 slot |
Head Bar: | - |
Air Shutter: | Full |
Manifold Pressure: | 3.5NG/3.4LP |
NOTES: | 3 through 5 section boilers require 8" extended front plate P/N 6022909 and burner adapter plate P/N 602292311 (order from Burnham) |