Gas Appliance OEM Settings Page
CHOOSE A DIFFERENT MANUFACTURER3CHOOSE A DIFFERENT APPLIANCE
Burnham (U.S. Boiler) V903A (447 MBH)
| Manufacturer: | Burnham (U.S. Boiler) |
| Appliance Series: | V |
| Appliance Model: | V903A |
| Burner Model: | 301GAS |
| Difusser: | B |
| Air Tube: | 14" B |
| OEM Air Tube #: | 99597 |
| Insertion Depth: | 4 1/8 |
| Input MBH: | 447 |
| Natural Gas Orifice: | 31/64 (.484) |
| Propane Orifice: | 25/64 (.391) |
| Air Setting: | 30NG/35LP |
| Air Band: | 4 slot |
| Head Bar: | - |
| Air Shutter: | Full |
| Manifold Pressure: | 3.5NG/3.4LP |
| NOTES: | 3 through 5 section boilers require 8" extended front plate P/N 6022909 and burner adapter plate P/N 602292311 (order from Burnham) |