Burnham (U.S. Boiler) V904A (606 MBH)
Manufacturer: | Burnham (U.S. Boiler) |
Appliance Series: | V |
Appliance Model: | V904A |
Burner Model: | 301GAS |
Difusser: | B |
Air Tube: | 14" B |
OEM Air Tube #: | 99597 |
Insertion Depth: | 4 1/8 |
Input MBH: | 606 |
Natural Gas Orifice: | 37/64 (.578) |
Propane Orifice: | 7/16 (.438) |
Air Setting: | 60NG/65LP |
Air Band: | 4 slot |
Head Bar: | - |
Air Shutter: | Full |
Manifold Pressure: | 3.5NG/3.6LP |
NOTES: | 3 through 5 section boilers require 8" extended front plate P/N 6022909 and burner adapter plate P/N 602292311 (order from Burnham) |