Gas Appliance OEM Settings Page
CHOOSE A DIFFERENT MANUFACTURER3CHOOSE A DIFFERENT APPLIANCE
Burnham (U.S. Boiler) V906A (1010 MBH)
Manufacturer: | Burnham (U.S. Boiler) |
Appliance Series: | V |
Appliance Model: | V906A |
Burner Model: | 601GAS |
Difusser: | 11 |
Air Tube: | 14" C |
OEM Air Tube #: | 99599 |
Insertion Depth: | 4 1/8 |
Input MBH: | 1010 |
Natural Gas Orifice: | |
Propane Orifice: | 5/8 (.625) |
Air Setting: | 4 |
Air Band: | -- |
Head Bar: | - |
Air Shutter: | -- |
Manifold Pressure: | 3.5 |
NOTES: | 3 through 5 section boilers require 8" extended front plate P/N 6022909 and burner adapter plate P/N 602292311 (order from Burnham) |