Burnham (U.S. Boiler) V907A (1198 MBH)
| Manufacturer: | |
| Appliance Series: | V |
| Appliance Model: | V907A |
| Burner Model: | 601GAS |
| Difusser: | |
| Air Tube: | 14" D |
| OEM Air Tube #: | 99600 |
| Insertion Depth: | 4 1/8 |
| Input MBH: | 1198 |
| Natural Gas Orifice: | 15/16 (.938) |
| Propane Orifice: | |
| Air Setting: | 5 |
| Air Band: | -- |
| Head Bar: | - |
| Air Shutter: | -- |
| Manifold Pressure: | 3.6 |