Gas Appliance OEM Settings Page

CHOOSE A DIFFERENT MANUFACTURER3


CHOOSE A DIFFERENT APPLIANCE

Dynatherm Boiler Manufacturing FP-48 (300 MBH)

Manufacturer:    Dynatherm Boiler Manufacturing
Appliance Series:    FP
Appliance Model:    FP-48
Burner Model:    201GAS
Difusser:    B
Air Tube:    10"
OEM Air Tube #:    99618
Insertion Depth:    3
Input MBH:   300
Natural Gas Orifice:    25/64 (.390)
Propane Orifice:    O (.316)
Air Setting:   65NG/75LP
Air Band:   2 Slot
Head Bar:   -
Air Shutter:    full
Manifold Pressure:    3.2NG/3.5LP
NOTES:   