Gas Appliance OEM Settings Page
CHOOSE A DIFFERENT MANUFACTURER3CHOOSE A DIFFERENT APPLIANCE
New Yorker Boiler Co. FR-122-W (150 MBH)
| Manufacturer: | New Yorker Boiler |
| Appliance Series: | FR |
| Appliance Model: | FR-122-W |
| Burner Model: | EZGas Pro |
| Difusser: | 9S |
| Air Tube: | 10" |
| OEM Air Tube #: | Universal |
| Insertion Depth: | 1 1/2 |
| Input MBH: | 150 |
| Natural Gas Orifice: | I (.272) |
| Propane Orifice: | A (.234) |
| Air Setting: | 50% |
| Air Band: | 1 Slot |
| Head Bar: | - |
| Air Shutter: | blank |
| Manifold Pressure: | 3.5 |
| NOTES: |