Gas Appliance OEM Settings Page

CHOOSE A DIFFERENT MANUFACTURER3


CHOOSE A DIFFERENT APPLIANCE

Solaia Boilers CSL6230 (322 MBH)

Manufacturer:    Solaia Boilers
Appliance Series:    CSL
Appliance Model:    CSL6230
Burner Model:    201GAS
Difusser:    D
Air Tube:    10"
OEM Air Tube #:    51057
Insertion Depth:    4 1/2
Input MBH:   322
Natural Gas Orifice:    5/8 (.625)
Propane Orifice:    15/32 (.469)
Air Setting:   85%
Air Band:   4 slot
Head Bar:   -
Air Shutter:    none
Manifold Pressure:    3.5
NOTES:    Solaia Series burners are built with covers and must have gasket under ignitor and grommet in access cover: kit # GSKTKIT5