Gas Appliance OEM Settings Page
CHOOSE A DIFFERENT MANUFACTURER3CHOOSE A DIFFERENT APPLIANCE
Columbia Boiler EMG-220 (220 MBH)
| Manufacturer: | Columbia Boiler |
| Appliance Series: | EMG |
| Appliance Model: | EMG-220 |
| Burner Model: | EZGas Pro |
| Difusser: | 9S |
| Air Tube: | 10"S |
| OEM Air Tube #: | 50659 |
| Insertion Depth: | 1 3/4 |
| Input MBH: | 220 |
| Natural Gas Orifice: | T (.358) |
| Propane Orifice: | 9/32 (.281) |
| Air Setting: | 56NG/70LP |
| Air Band: | 2 slot |
| Head Bar: | - |
| Air Shutter: | blank |
| Manifold Pressure: | 3.5 |
| NOTES: |