Gas Appliance OEM Settings Page

CHOOSE A DIFFERENT MANUFACTURER3


CHOOSE A DIFFERENT APPLIANCE

Columbia Boiler EMG-31-120 (120 MBH)

Manufacturer:    Columbia Boiler
Appliance Series:    EMG
Appliance Model:    EMG-31-120
Burner Model:    EZGas Pro
Difusser:    9S
Air Tube:    10"S
OEM Air Tube #:    50659
Insertion Depth:    1 3/4
Input MBH:   120
Natural Gas Orifice:    C (.242)
Propane Orifice:    11/64 (.172)
Air Setting:   31%
Air Band:   1 slot
Head Bar:   -
Air Shutter:    blank
Manifold Pressure:    3.5
NOTES:   
Go to Top