Gas Appliance OEM Settings Page

CHOOSE A DIFFERENT MANUFACTURER3


CHOOSE A DIFFERENT APPLIANCE

Thermo-Dynamics Boiler Co. HT-II-165 (225 MBH)

Manufacturer:    Thermo-Dynamics Boiler Co.
Appliance Series:    HT-II
Appliance Model:    HT-II-165
Burner Model:    EZGas Pro
Difusser:    A
Air Tube:    10"
OEM Air Tube #:    Universal
Insertion Depth:    3 3/4
Input MBH:   225
Natural Gas Orifice:    11/32 (.344)
Propane Orifice:    9/32 (.281)
Air Setting:   50%
Air Band:   2 Slot
Head Bar:   -
Air Shutter:    blank
Manifold Pressure:    3.5
NOTES:   