Gas Appliance OEM Settings Page
CHOOSE A DIFFERENT MANUFACTURER3CHOOSE A DIFFERENT APPLIANCE
Thermo-Dynamics Boiler Co. TDX-160-DV (160 MBH)
| Manufacturer: | Thermo-Dynamics Boiler Co. |
| Appliance Series: | TDX |
| Appliance Model: | TDX-160-DV |
| Burner Model: | EZGas Pro |
| Difusser: | B |
| Air Tube: | 12"/ 10" |
| OEM Air Tube #: | 50171 |
| Insertion Depth: | 1 3/4 |
| Input MBH: | 160 |
| Natural Gas Orifice: | L (.290) |
| Propane Orifice: | 15/64 (.234) |
| Air Setting: | 82NG/85LP |
| Air Band: | 1 slot |
| Head Bar: | - |
| Air Shutter: | blank |
| Manifold Pressure: | 3.5 |
| NOTES: |