Gas Appliance OEM Settings Page
CHOOSE A DIFFERENT MANUFACTURER3CHOOSE A DIFFERENT APPLIANCE
Utica Boilers SFH4100 (140 MBH)
| Manufacturer: | Utica Boilers |
| Appliance Series: | SFH |
| Appliance Model: | SFH4100 |
| Burner Model: | EZGas Pro |
| Difusser: | 9S |
| Air Tube: | 10" |
| OEM Air Tube #: | Universal |
| Insertion Depth: | 2 1/2 |
| Input MBH: | 140 |
| Natural Gas Orifice: | 17/64 (.265) |
| Propane Orifice: | 7/32 (.219) |
| Air Setting: | 25% |
| Air Band: | 2 slot |
| Head Bar: | - |
| Air Shutter: | blank |
| Manifold Pressure: | 3.5 |