Gas Appliance OEM Settings Page
CHOOSE A DIFFERENT MANUFACTURER3CHOOSE A DIFFERENT APPLIANCE
Weil-McLain UO-4 (168 MBH)
| Manufacturer: | Weil-McLain |
| Appliance Series: | UO |
| Appliance Model: | UO-4 |
| Burner Model: | EZGas Pro |
| Difusser: | B |
| Air Tube: | 10"S |
| OEM Air Tube #: | 50330 |
| Insertion Depth: | 2 |
| Input MBH: | 168 |
| Natural Gas Orifice: | L (.290) |
| Propane Orifice: | D (.246) |
| Air Setting: | 65% |
| Air Band: | 1 slot |
| Head Bar: | - |
| Air Shutter: | blank |
| Manifold Pressure: | 3.5 |
| NOTES: | Ultra burners are built with covers, Must have gasket under ignitor and grommet in access cover: kit # GSKTKIT3 |