CHOOSE A DIFFERENT MANUFACTURER 6


CHOOSE A DIFFERENT APPLIANCE

Boyertown Furnace Co. RSM-600 (Nozzle Size: 0.60)

ALL BLENDS (#2-B100) SETTINGS

Manufacturer:    Boyertown Furnace Co.
Appliance Series:    Regal Star Furnace
Appliance Model:    RSM-600
Burner Model:    EZ-LF
Air Tube:    9" 12D
OEM Air Tube #:    50796
Insertion Depth:    4.25
Nozzle GPH:   0.60
Nozzle Type:    60A
Nozzle Mfr:    Delavan
Alternative Nozzle Type:    60W
Alternative Nozzle Mfr:    Delavan
Pump PSI:   165
Air Shutter:    Blank
Head Position:    [GPH 0.60/0.65] - (Position 1)
Air Setting:    45%
NOTES:   


B100 Field Conversion Guide

Use the below steps to convert a burner mfg before 11/20/2023 for optimization with all blends.

  1. Change Combustion Head Assembly* – Use Part No 77974S
    * Make sure combustion head has a gold C-clip (which designates that it is our B100 design.)
  2. Check/Replace Pump – Install Suntec Pump #3006B rated for B100
  3. Make changes highlighted in green above
  4. Check/Replace Control – Install ProX 70200 if the burner does not already have one.
  5. Check/Change Settings on ProX 70200**:
    • Flame stabilization:  5 seconds
    • CAD Ohms Max: 5300
    • Ignition Type: Smart Ignition
    • Motor Delay Off (Post-Purge): Minimum 15 seconds


** ProX 70200 controls manufactured after 11/20/23 will already have these settings.
Go to Top