Class Boilers CL6150

ALL BLENDS (#2-B100) SETTINGS

Manufacturer:    Class Boilers
Appliance Series:    CL
Appliance Model:    CL6150
Burner Model:    EZ-1HP
Air Tube:    4" EZ-1
OEM Air Tube #:    50926
Insertion Depth:    4
Nozzle GPH:   1.25
Nozzle Type:    45B
Nozzle Mfr:    Delavan
Alternative Nozzle Type:    60B
Alternative Nozzle Mfr:    Delavan
Pump PSI:   150
Air Shutter:    Blank
Head Position:    [GPH 1.10/ 1.25] or (Position 4)
Air Setting:    [1.25 GPH] or (95% Open)
NOTES:   


B100 Field Conversion Guide

Use the below steps to convert a burner mfg before 11/20/2023 for optimization with all blends.

  1. Change Combustion Head Assembly* – Use Part No 77941S
    * Make sure combustion head has a gold C-clip (which designates that it is our B100 design.)
  2. Check/Replace Pump – Install Suntec Pump #3006B rated for B100
  3. Make changes highlighted in green above
  4. Check/Replace Control – Install ProX 70200 if the burner does not already have one.
  5. Check/Change Settings on ProX 70200**:
    • Flame stabilization:  5 seconds
    • CAD Ohms Max: 5300
    • Ignition Type: Smart Ignition
    • Motor Delay Off (Post-Purge): Minimum 15 seconds


** ProX 70200 controls manufactured after 11/20/23 will already have these settings.