CHOOSE A DIFFERENT MANUFACTURER 6


CHOOSE A DIFFERENT APPLIANCE

Crown Boiler Company CHC 68-96C (Nozzle Size: 0.50)

ALL BLENDS (#2-B100) SETTINGS

Manufacturer:    Crown Boiler Company
Appliance Series:    CHC
Appliance Model:    CHC 68-96C
Burner Model:    EZ-1HP
Air Tube:    7" EZ-1
OEM Air Tube #:    98625
Insertion Depth:    5.875
Nozzle GPH:   0.50
Nozzle Type:    60A
Nozzle Mfr:    Delavan
Alternative Nozzle Type:   
Alternative Nozzle Mfr:   
Pump PSI:   140
Air Shutter:    Blank
Head Position:    [GPH 0.50] or (Position 0)
Air Setting:    [0.45 GPH] or (25% Open)
NOTES:   


B100 Field Conversion Guide

Use the below steps to convert a burner mfg before 11/20/2023 for optimization with all blends.

  1. Change Combustion Head Assembly* – Use Part No 77966S
    * Make sure combustion head has a gold C-clip (which designates that it is our B100 design.)
  2. Check/Replace Pump – Install Suntec Pump #3006B rated for B100
  3. Make changes highlighted in green above
  4. Check/Replace Control – Install ProX 70200 if the burner does not already have one.
  5. Check/Change Settings on ProX 70200**:
    • Flame stabilization:  5 seconds
    • CAD Ohms Max: 5300
    • Ignition Type: Smart Ignition
    • Motor Delay Off (Post-Purge): Minimum 15 seconds


** ProX 70200 controls manufactured after 11/20/23 will already have these settings.
Go to Top